Lesson 10: Circuits for real-life purposes

Is the power board overloaded?

SkillsCircuits for real-life purposesPower and electrical energyParallel circuits

Worked example

  • Complex unfamiliar
  • Technology active

On a 40 °C day, a student runs a 1.5 kW portable air conditioner, a 0.40 kW gaming computer and a 0.15 kW television from one power board plugged into a 230 V socket. The power board is rated at 10 A.

(a) Calculate the current in the power board's lead. (b) The student wants to add a 0.90 kW portable air conditioner for a second room. Would the board be overloaded? (c) What is the most extra power the board could safely supply?

1 of 5 steps
  1. Step 1: Add the powers

    P=1.5+0.40+0.15=2.05 kW=2050 WP = 1.5 + 0.40 + 0.15 = 2.05\unit{kW} = 2050\unit{W}

Try a similar one

A fresh question of the same kind, checked as you answer, with hints and a full solution.

Method

  1. Parallel appliances: add the powers (or the currents).

  2. Total current from I=PVI = \dfrac{P}{V}.

  3. Compare with the rating; spare power is the rated power minus the power in use.

Watch out for

  • Working with kilowatts in I=PVI = \frac{P}{V} gives a current a thousand times too small.

  • Thinking the new device only shares the existing current. Each parallel branch adds its own current.